A Farwest Corrosion Control Company

Home Products Contact Us Request Quote Order Online

 
 

 Navigation: CCP Home > Products > Insulators & Seals > Link Seal Modular Seals

Link-Seal® Modular Seals
Sizing Procedure 2 for Pipe Sizes
that Do Not Appear in Charts


If your pipe size does not appear in the charts on pages, use the following
method to select the correct Link-Seal® modular seal for your application.

Method 2 - Link-Seal® Modular Seal Sizing

If your pipe size does not appear in the charts for standard pipe sizes, use the following method to select the correct Link-Seal® modular seal for your application.

  1. Calculate the annular space. The annular space is half the difference between the actual pipe O.D. and the actual wall I.D. opening diameter. Use the following formula:

Annular Space = (Wall Opening I.D. - Actual Pipe O.D.) / 2

  1. From the charts below, select the size closest to the annular space calculated in step 1. You have selected the correct size Link-Seal® modular seal if....the free state thickness is less than the annular space...and the expanded state thickness is greater than the annular space.

  1. Calculate the number of links required to fit around the pipe and seal the annular space.

A. Determine the bolt circle for your Link-Seal® modular seal assembly by using the following formula:

Bolt Circle = (Wall Opening I.D. + Pipe Diameter O.D.) / 2

B. Find the Link-Seal® modular seal chord length (Column 4) and use the following formula to determine required number of links per Link-Seal® modular seal assembly.

Links Per Seal = (Bolt Circle x 3.14) / Chord Length

The result must be rounded down to the next whole number. The figures are accurate if the calculation results in 13 or more links per belt. If the results are fewer than 13 links verify using the linked verification charts below.

Verification charts for Link-Seal LS-200 through LS-360
 

Verification charts for Link-Seal LS-400 through LS-600

Example:

Wall Opening I.D. = 12”
Actual Pipe O.D. = 9.05”

Calculate the annular Space as (12 - 9.05) / 2 = 1.475

Select the Link-Seal® modular seal size closest to the annular space. LS-400 is chosen from the chart, because 1.475” falls between 1.43 and 1.81 (the free state and expanded state thickness).

Determine the number of links for a complete assembly:

Bolt circle = (12 + 9.05) / 2 = 10.525
Chord length for LS-400 = 3.635"
Links per seal = (10.525 x 3.14) / 3.625 = 9.12
Round down links per seal to 9.

Since the final calculation results in fewer than 13 links, it is advisable to verify the accuracy of the calculation by using the verification charts.
 

Corrosion Control Products Company

  

Corrosion Control Products Resources

 Search this Website
 Request Quote
 Order Products Online
 3-Ring Binder Catalog
 Industry Links
 CCP Suppliers
 Installation Guides
 MSDS
  

Farwest Cathodic
Protection Products
& Materials

  

Home

Products Search Request Quote Order Online

Corrosion Control Products Company
800-421-2623

Tel: 

 310-532-9314
Fax:  310-532-1472

1480 West Artesia Blvd., Gardena, CA 90248-3215, USA
 www.ccpco.com

© 1996-2009 Corrosion Control Products Company | Privacy Statement
 

Integrity – Service – Quality
                  
... Since 1956