Farwest Corrosion
Control Company
 

Home Products Services Contact Us Search Request Quote Order Online
 

    
PLATTLINE
Zinc Ribbon Anodes for AC Mitigation

platt04.jpg (29827 bytes)

Figure 1. Plattline zinc ribbon anodes
used for AC mitigation

Plattline zinc ribbon anodes should be used when overhead high voltage transmission lines share a corridor with an underground pipeline.

Bare zinc conductors, buried parallel to a pipeline and regularly connected to it, are effective in mitigating pipeline potentials due to inductive and conductive interference.

Overview

The long-term trend in the United States and many other countries is shared land use for pipelines and other utilities. This movement has increased the number of overhead high voltage transmission lines parallel to and sharing a corridor with an underground pipeline. This combination has increased the need for grounding of the pipeline to dissipate interference.

In these systems, A.C. voltages are transmitted 1° the pipeline by conductive or inductive interference. Magnetic induction acts along the pipeline or pipeline segment that is approximately parallel to the power line and can cause significant pipeline potentials even at relatively large separation distances.

Consideration must be given to safety of personnel and the public who may come into contact with above ground portions of the pipeline such as valves and test stations. These exposed structures can be a potential shock hazard when touched while the soil is at a significantly different potential.

Advances in interference control have resulted in the gradient control wire method. This method consists of one or more bare zinc conductors buried parallel to and near the pipeline and regularly connected to it. Plattline™ zinc ribbon anode used in this way is very effective in mitigating excessive pipeline potentials due to both inductive and conductive interference. (See Figures ] & 2.) Plattline evens out pipeline and soil potential differences. Additionally, Plattline can provide cathodic protection to the pipeline.

It is important to review the use and design of a gradient control wire system with an engineer experienced with this system, as its performance will depend on the multilayered structure of the earth.

For inductive interference, gradient control wires provide additional grounding for the pipeline and decrease the induced pipe potential rise. At the same time, they raise local ground potentials, thus sharply reducing touch potentials and coating stress voltages.

For conductive interference, gradient control wires dampen the soil potential rise close to the pipe while raising pipe potentials, thus providing reduced touch voltages and decreasing coating stress voltages.

Life expectancy of Plattline in this application would be quite long and would generally be determined by Plattline as a projected cathodic protection system. The most common sizes of Plattline for AC mitigation are plus and standard.

Plattline can provide a significant means to mitigate potential gradients along the length of a pipeline. Importance must also be placed on reducing the potentials at valve sites, metering stations, pig launchers and receivers and other accessible installations for worker safety.

Gradient control grids or grounding mats raise local ground potentials in the same way gradient control wires do. These grounding mats can be made in several forms. Spiral and rectangular designs are generally standard for grounding mats. These are shown in Figures 3, 4 and 5. The most common size of Plattline for grounding mats is standard.

Reference should be made to NACE Standard RP0177 (Latest Revision) - Recommended Practice on Mitigation of Alternating Current & Lightning Effects on Metallic Structure and Corrosion Control Systems. Also, ANSI/IEEE Standard 80 specifies safety design criteria for determining maximum acceptable touch and step voltages during fault conditions.

Finally, during fault conditions on the power line, the system must ensure that pipeline coating stress voltages remain within acceptable limits to prevent coating damage and damage to the pipeline steel. Coating damage can occur in the range of 1000 - 2000 volts for bitumen based coatings and in the range of 3000 - 5000 volts for polyethylene or fusion-bonded epoxy coated pipelines.

Product Specifications

Plattline™ zinc ribbon anodes are used in a variety of applications. They are used for cathodic protection on buried pipelines, for AC mitigation on pipelines, for sacrificial cathodic protection of secondary bottoms on above-ground storage tanks, for AC mitigation grounding mats and for other corrosion protection applications.
  

Product
Size

platt09.gif (1631 bytes)
Super

platt10.gif (1406 bytes)
Plus

platt11.gif (1245 bytes)
Standard

platt12.gif (1085 bytes)
Small

  Cross section 1" x 1-¼"
25.4 x 31.75 mm
5/8" x 7/8"
15.88 x 22.22 mm
1/2" x 9/16"
12.7 x 14.28 mm
11/32" x 13/32"
8.73 x 10.32 mm
  Weight 2.4 lbs/ft
3.570 kg/m
1.2 lbs/ft
1.785 kg/m
0.6 lbs/ft
0.8925 kg/m
0.25 lbs/ft
0.372 kg/m
  Diameter of
  wire core
0.185"
4.70 mm
0.135"
3.43 mm
0.130"
3.30 mm
0.115"
2.92 mm
  Coil length,
  standard
100 ft
30.5 m
200 ft
61 m
500 ft
152 m
1000 ft
305 m
  Coil I.D.,
  standard
36"
91.44 cm
36"
91.44 cm
12"
30.5 cm
12"
30.5 cm
  Packaging Steel banded, random wound open coils. Steel banded, random wound open coils. Wood reels Wood reels
  
   Footnotes to Specification Table
  1. All dimensions and weights are nominal.
  2. Galvanized Steel.
  3. "Arctic" standard size has nominal core diameter of .163" (4.140 mm).
  4. Longer coil lengths are available on special order.
  5. Standard size also available in reels of 1000 ft and 3600 ft.
  6. Plattline I is an alloyed zinc product and is generally used in seawater or brackish water systems. It meets the chemical requirement of MIL-A-18001K and ASTM B418-95a Type I.
  7. Plattline II is a high purity product and generally used in underground and fresh water systems. It meets the chemical requirements of ASTM B418-95a Type II.
      

Cathodic Protection Products & Materials

 Impressed Anodes
 Sacrificial Anodes
 Cable & Splicing
 DC Supplies & Rectifiers
 Remote Monitoring
 Polarization Cells
 Overvoltage Protection
 Junction & Bond Boxes
 Test Stations & Markers
 Reference Electrodes
 Test Instruments
 Insulating Materials
 Pipe Coatings & Tape
 Miscellaneous Products

  

Cathodic Protection Services

 Farwest Engineering
 Farwest Installation

  

Cathodic Protection of Offshore Structures

 Galvanic CP Systems
 Impressed CP Systems
 Attachment Systems
 Monitoring Equipment

  

Marine Products Division

 Marine ICCP Systems
 Galvanic CP Materials
 Marine Growth Protection
 Electrolytic De-Scaling
 Electro-Chlorination

  

Pipeline Protection Products Division

 Epoxy Coatings
 Heat-Shrink Coatings
 Mastic Coatings
 Petrolatum Coatings
 Tape Coatings
 Surface Decontamination
 Moisture Seal Products
 Rockshields
 Inspection Instruments
 Insulated Fittings
 Insulators & Seals
 Pipeline Casing Fillers
 Flange Insulation
 Pipeline Cleaning Pigs
 Composite Systems
 Accessory Products
  

More Farwest
Website Resources

 Search this Website
 Request Quote
 Order Products Online
 View PDF Catalog
 Industry Links
 Farwest Suppliers
 Industry News
 Employment
 

Home

Products Services Search Request Quote Order Online

Farwest Corrosion Control Company
888-532-7937   (888-5FARWEST)

Tel: 

 310-532-9524
Fax:  310-532-3934

1480 West Artesia Blvd., Gardena, CA 90248-3215, USA
 www.farwestcorrosion.com

© 1996-2008 Farwest Corrosion Control Company | Privacy Statement
 

Integrity – Service – Quality
                  
... Since 1956