Navigation:
Home >
Products >
Polarization Cells & Overvoltage
Protection
SSD
Accessories for
Solid State Ground Mat Decoupler
by Dairyland Electrical
Industries

Used with
DEI SSD Solid State Ground Mat Decoupler

|
MTF
Flange Mounting Bracket
The SSD or OVP2 can be
mounted across an insulated flange using an existing
flange bolt, usually at the top center position on the
flange (See Attached Drawings). In order to install
these devices using existing flange bolts, the flange
must have a machined outer face in order to mate to the
bus bars.
To order a complete kit
to flange mount using flange bolts, customers must also
provide the pipe diameter and the ANSI LB class. All MTF
flange mounting kits include brackets, nuts,
bolts and washers necessary for installing the device.
Specifications:
Material: #110 Copper
Plating: Nickel Electroplated
Thickness: 0.095" |
 |

|
MTT
Mounting Kit
Mounting the SSD or OVP2
to a flange can be accomplished via drilling and tapping
the edge of the flange for a 5/16-18x1” or M8-1.25x20mm
fully-threaded stud with jam nuts, or by pin brazing an
M8x16 stud to each flange. Verify that the dimensions of
either of these mounting arrangements are suitable for
the flange before ordering. For mounting using tapped
holes and studs, specify DEI part number MTT-516 for the
5/16” threaded studs, or MTT-M8 for the M8 threaded
studs.
Specifications:
Material: #110 Copper
Finish: Nickel Electroplated
Thickness: 0.094" |
 |

|
MTS
Mounting Kit
If mounting via pin
brazed studs is desired, mount the device by using a
M8x16 stud pin brazed to each side of the flange. The
MTS kit provided by DEI includes “L” brackets, nuts,
bolts, washers for each side of the flange. DEI does not
supply the M8 stud kit or ceramic sleeve needed for this
installation. Please order these parts from the
manufacturer / distributor of the pin brazing equipment
being used. Verify that the dimensions for this mounting
arrangement are suitable for the flange before ordering.
Specifications:
Material: #110 Copper
Finish: Nickel Electroplated
Thickness: 0.094" |
 |

|
MTL
Lead Kit
Connection of an SSD or
OVP2 normally uses #6 AWG insulated leads with
compression terminals. Each lead has a factory installed
compression terminal on one end with the other lead end
left unfinished for cutting to the shortest feasible
length during installation. (The required 5/16" bolts,
nuts and washers to attach the leads to the device are
furnished with each decoupler.) The standard lengths are
12 inches (300mm) and 36 inches (900mm).
Specify part number
MTL-6-12 or MTL-6-36 for a set of two conductors with
12" or 36" lengths, respectively. For custom lengths,
specify MTL-6-"X" and specify the units for "X." If a
terminal is required for the unfinished end of the lead,
contact DEI.
Note: For
any model with an AC fault current rating equal to or
greater than 2 kA or for use with a Gradient Control
Mat, two leads per terminal are required. If one set of
leads is to be connected to a DEI furnished Gradient
Control Mat, then the lead-to-mat connection will be
thermit welded. See DEI information on Gradient Control
Mats for connection details.
|

|
Hex Coupling
Nut
Pin brazed studs are a
convenient mounting method for the model SSD, attaching
the decoupler to a pipe wall. Decoupler terminal
connections can be made using insulated conductors,
however total length should be minimized to limit the
inductive over-voltage effects from lightning. One
method of limiting conduction path length when also
using 8mm pin brazed studs is the DEI Hex Coupling Nut,
which attaches one SSD terminal to the pipe wall. The
other SSD terminal utilizes an insulated flexible
conductor (such as the MTL Kit) for attachment to the
opposite structure (ground, etc). |
 |

|
42"
Fiberglass Pedestal
Where a free-standing
enclosure is desired for the DEI model SSD or OVP2, the
42" fiberglass pedestal is ideal. Requiring no
foundation or mounting structure, the Pedestal is
installed by partially burying the lower one-half in the
soil. Cable entrance is via the open bottom area of the
lower one-half, which is ideal for AC mitigation
applications. The padlockable hasp prevents unauthorized
access. All mounting hardware required to attach the
decoupler in the pedestal will be packaged with the SSD
or OVP2. To order, specify Pedestal-42" plus the desired
decoupling device.
Specifications:
Color: Light Green
Nominal fiberglass thickness (3/16" (4.8mm)
Exterior UV stabilized gelcoat 14 Mill (0.36mm) thick
Fire retardant. Does not support combustion.
Stainless steel hardware |
 |
|