Fluke
80i-110s AC/DC Current Clamp
- Current Ranges:
0.1A to 100A DC or 0.1 to 70A AC
- Basic Accuracy,
DC to 1kHz:
100 mV/A setting: 50 mA to 10A
±
3% of reading + 50mA
10 mV/A setting: 50 mA to 40A
±
4% of reading + 50mA
40A to 80A:
±
12% of reading + 50mA
80 to 100A:
±
15% of reading
- Output Signal:
10A range: 100 mV/A
100A range: 10 mV/A
- Bandwidth:
1 Hz to 20 kHz
- Working Voltage:
600V AC rms
- Maximum Conductor
Sizer: 11.8 mm (0.46").
- Safety Rating:
IEC 1010 and CSA-C22.2 No. 1010-1, Installation
Category II, Working Voltage 600V.
- Compatibility:
Any meter with a BNC input. Can be used with DMMs
with optional PM9081/001 BNC to Banana plug adapter.
|
 |
Fluke i200 Small Size AC Current Clamp
- Current Range:
0.5A to 200A
- Maximum
Non-Destructive Current: 240A
- Lowest Measurable
Current: 0.5A
- Basic Accuracy:
1% of reading + 0.5A (48-65 Hz)
- Usable Frequency:
40 Hz to 10 kHz
- Output Level:
1 mA/A
- Maximum Conductor
Size: 20 mm diameter
- Compatibility:
Any DMM that accepts 4 mm-shrouded banana plugs and
has an AC mA scale.
|
 |
Fluke i200s Small Size AC Current Clamp
- Current Ranges:
0.1A to 20A, 0.5A to 200A
- Maximum
Non-Destructive Current: 240A
- Lowest Measurable
Current: 0.1A
- Basic Accuracy:
1.5% of reading +0.5 A (48-65 Hz)
- Usable Frequency:
40 Hz to 10 kHz
- Output Level: 100
mV / A, 10 mV / A
- Maximum Conductor
Size: 20 mm (0.78") diameter
- Compatibility:
Any instrument with a BNC input connector or accepts
4 mm-shrouded banana plugs. A dual banana to BNC
adapter is supplied.
|
 |
Fluke i400 AC High Safety Current Clamp
- Current Range:
1A to 400A
- Maximum
Non-Destructive Current: 1000A
- Lowest Measurable
Current: 1A
- Basic Accuracy:
2% of reading + 0.06A (45-400 Hz)
- Usable Frequency:
5 Hz to 20 kHz
- Output Level: 1
mA/A
- Maximum Conductor
Size: 32 mm (1.25") diameter
- Safety: Isolated
to 1000V AC rms from earth to ground. Soft
non-slippery over-mold handle prevents from
accidental touching live wiring
- Compatibility:
Any DMM that accepts 4 mm-shrouded banana plugs and
has an AC mA scale.
|
 |
Fluke i800 AC Current Clamp Probe
- Current Range:
100 mA to 800A rms
- Maximum
Non-Destructive Current: 1500A rms (50/60
Hz)
- Lowest Measurable
Current: 100 mA
- Voltage Rating:
CAT III 600 V
- Basic Accuracy:
±1% of reading
- Usable Frequency:
30 Hz to 10 kHz (-3dB)
- Output Level:
1 mA / A
- Maximum Conductor
Size: 54 mm (2.1") diameter
- Compatibility:
Any DMM that accepts 4 mm-shrouded banana plugs and
has an AC mA scale.
|
 |
Fluke i1000s Large AC Current Probe
- Current Ranges:
0.1A to 10A, 0.1A to 100A, 100A, 1A to
1000A
- Maximum
Non-Destructive Current: 2000 A
- Lowest measurable
current: 0.1A
- Basic Accuracy:
1% of reading + 1A, (48-65 Hz)
- Usable Frequency:
5 Hz - 100 kHz
- Output Levels:
100 mV/A, 10 mV/A, 1 mV/A
- Maximum Conductor
Size: 54 mm (2-1/8") diameter
- Compatibility:
Connects directly to an oscilloscope through a
reinforced coaxial cable and an insulated BNC
connector. Can be used with DMMs with optional
PM9081/001 BNC to Banana adapter.
- Applications: Ideal
for measuring distorted current waveforms and
harmonics up to 100 kHz without breaking the
circuit. A passive filter eliminates noise and ring
on rapidly rising dI/dt waveforms.
|
 |
Fluke
i1010
AC/DC Current Clamp
- Current Ranges:
1A to 600A AC or 1A to 1000 A DC
- Maximum
Non-Destructive Current: 1000A
- Lowest Measurable
Current: 0.5A
- Basic Accuracy:
2% of reading + 0.5A
- Usable frequency:
DC - 10 kHz
- Measurement Type:
Hall sensor
- Output level:
1 mV/A
- Zero Error
Adjustment: Yes
- Maximum Conductor
Size: 30 mm diameter or 2 x 25 mm
- Compatibility:
Any meter with a banana plug input.
|
 |
Fluke i1010-KIT AC/DC Current Clamp Kit
Special value kit for
electrical professionals looking to add on DC and AC
current measurement capabilities to their DMM.
Includes a roomy carrying case to hold and protect
the DMM and current clamp, plus extra storage for
test leads, probes and manuals. Included with kit:
- i1010 AC/DC
Current Clamp
- Zippered vinyl
carrying case with moveable divider
|