DIMENSIONS
Height to top of lid 6 3/4”
Overall height 8 1/4”
Width at bottom 4 5/16”
Width at top 5 1/4”
Depth at bottom 4 5/16”
Depth at top 5 1/4”
As the applied Electromagnetic Field (EMF) across the cell terminals increases, current flow through the Kirk Cell will increase in general agreement with the data in the Performance tables below. Actual current flow will vary with ambient conditions including but not limited to: temperature, solution concentration and age.
K-5A KIRK CELL PERFORMANCE TABLE
Delta E Apparent
Across Cell Resultant Internal
Terminals Current Impedance
(Volts) Flow (Ohms)
_______________________________________________________________
DIRECT CURRENT DATA
0.39 100ua 3900
0.64 1ma 640
0.71 2ma 355
0.785 3ma 262
0.84 4ma 210
0.97 5ma 194
1.20* 6ma 200
1.26 7ma 180
1.30 8ma 163
1.34 9ma 148
1.42 10ma 142
1.48 15ma 99
1.70 20ma 85
1.72 25ma 69
1.73 30ma 58
1.73 40ma 43
1.74 50ma 35
1.77 100ma 18
1.87 500ma 3.7
1.90 1A 1.9
1.99 5A 0.4
2.10 10A 0.21
2.85 100A 0.029
4.85 500A 0.0097
ALTERNATING CURRENT DATA
0.30 500ma 0.60
0.38 1A 0.38
0.67 5A 0.13
0.90 10A 0.09
1.15 50A 0.02
1.50 100A 0.015
3.80 500A 0.0076
*Leakage threshold
K-25 KIRK CELL
DIMENSIONS
Height to top of lid 15 1/8”
Overall height 16 3/4”
Width at bottom 11 1/8”
Width at top 12 1/16”
Depth at bottom 9 7/16”
Depth at top 10 1/16”
As the applied Electromagnetic Field (EMF) across the cell terminals increases, current flow through the Kirk Cell will increase in general agreement with the data in the Performance tables below. Actual current flow will vary with ambient conditions including but not limited to: temperature, solution concentration and age.
K-25 KIRK CELL PERFORMANCE TABLE
Delta E Apparent
Across Cell Resultant Internal
Terminals Current Impedance
(Volts) Flow (Ohms)
_______________________________________________________________
DIRECT CURRENT DATA
0.275 100ua 2750
0.47 1ma 470
0.52 2ma 260
0.56 3ma 187
0.58 4ma 145
0.63 5ma 126
0.73 6ma 122
0.79 7ma 113
0.825 8ma 103
0.85 9ma 94
0.88 10ma 88
0.94 15ma 63
1.00 20ma 50
1.08 25ma 43
1.26* 30ma 42
1.55 40ma 39
1.66 50ma 33
1.68 100ma 17
1.72 500ma 3.4
1.76 1A 1.8
1.86 5A 0.37
1.90 10A 0.19
ALTERNATING CURRENT DATA
0.02 0.5A 0.04
0.04 1A 0.04
0.06 5A 0.01
0.30 10A 0.03
*Leakage threshold
DIMENSIONS
Height to top of lid 15 1/8”
Overall height 16 3/4”
Width at bottom 11 1/8”
Width at top 12 1/16”
Depth at bottom 9 7/16”
Depth at top 10 1/16”
As the applied Electromagnetic Field (EMF) across the cell terminals increases, current flow through the Kirk Cell will increase in general agreement with the data in the Performance tables below. Actual current flow will vary with ambient conditions including but not limited to: temperature, solution concentration and age.
K-50 KIRK CELL PERFORMANCE TABLE
Delta E Apparent
Across Cell Resultant Internal
Terminals Current Impedance
(Volts) Flow (Ohms)
_________________________________________________________________
DIRECT CURRENT DATA
0.15 100ua 1500
0.38 1ma 380
0.42 2ma 210
0.45 3ma 150
0.46 4ma 115
0.48 5ma 96
0.50 6ma 83
0.52 7ma 74
0.53 8ma 66
0.55 9ma 61
0.59 10ma 59
0.69 15ma 46
0.86 20ma 43
0.925 25ma 37
1.00 30ma 33
1.16 40ma 29
1.20* 50ma 24
1.30 100ma 13
1.72 500ma 3.4
1.76 1A 1.8
1.82 5A 0.36
1.85 10A 0.19
2.15 100A 0.022
2.65 500A 0.053
3.15 1KA 0.0032
ALTERNATING CURRENT DATA
0.01 500ma 0.02
0.02 1A 0.02
0.04 5A 0.01
0.20 10A 0.02
0.58 50A 0.012
0.62 100A 0.0062
1.30 500A 0.0026
10.6 14KA 0.00076
12.5 38.5KA 0.00032
14.0 44.0KA 0.00032
15.0 52.5KA 0.00029
17.0 58.0KA 0.00029
19.9 64.0KA 0.00031
*Leakage threshold